RDL RU-SQ6A Six-Step Power Sequencing Controller
The RU-SQ6A runs power-up and power-down sequences of up to six steps. Each step has an open-collector output and an SPST dry relay contact, and a front TIMING INTERVAL knob sets the delay between steps from 1 to 10 seconds. Front LEDs show each channel turning on and off, and the Sure-Lok supervisory circuit holds the outputs on once the sequence completes.
A rear switch selects front-panel or remote control; in remote mode, grounding the ACTIVATE terminals starts the up sequence and releasing them runs it down in reverse. Control and output wiring connects on labeled detachable terminal blocks on the rear panel. The module needs 24 Vdc. RDL recommends its PS-24AS power supply (PS-24AX outside the USA), not included.
- DimensionsHeight: 1.7 in. 4.3 cm; Length: 5.8 in. 15.0 cm
- Interval Between Outputs1 to 10 seconds nominal, front-panel adjustable
- Relay Outputs (6)SPST (closed when active)
- Control InputExternal closure < 2.5 mA @ 24 Vdc
- Maximum Switching Power60 W (220 Vdc, 125 Vac, 2A)
| Part Number | RU-SQ6A |
|---|---|
| Interval Between Outputs | 1 to 10 seconds nominal, front-panel adjustable |
| Relay Outputs (6) | SPST (closed when active) |
| Maximum Switching Power | 60 W (220 Vdc, 125 Vac, 2A) |
| Maximum Switching Current | 2 A |
| Open Collector (6) | 200 mA surge; 50 mA continuous; 200 mA maximum |
| Control Input | External closure < 2.5 mA @ 24 Vdc |
| Power Requirement | 24 Vdc @ 100 mA (plus total load current connected to 24 Vdc output) |
| Dimensions | Height: 1.7 in. 4.3 cm; Length: 5.8 in. 15.0 cm; Depth: 3.45 in. 8.8 cm |